PDF
Standards Pools 2018
LHAP 302A-61-40680 (FA25) - Water and Light/Introductory Information/Standards Pools 2018.pdf
Resource Viewer
Preview or play this resource here.
Extracted PDF Text
Extracted from the original source file.
Page 1
Alberta Health
Pool Standards
July 2014 (Amended January 2018)
Page 2
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 2
Government of
Alberta Department
Alberta Health
Title Pool Standards, July 2014 (Amended January 2018)
Author Public Health and Compliance
Authority Section 66(4) of the Public Health Act, and Section 2 of the Public
Swimming Pools Regulation A.R. 204/2014, as amended.
Effective Date January 1, 2018
Superseded
Documents
Pool Standards, July 2014 (Amended 2017)
Contact The Pool Standards, July 2014 (Amended January 2018) can be
found on the Open Alberta website:
https://open.alberta.ca/publications/9781460137215
For general information, call Alberta Health Central Reception
at 780-427-7164 and your call will be directed to the appropriate
personnel.
ISBN ISBN 978-1-4601-3721-5 (Online)
Page 3
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 3
Table of Contents
Table of Contents .................................................................................................. 3
Part 1 Purpose and Application .......................................................................... 5
Part 2 Definitions ................................................................................................ 6
Part 3 Operation and Maintenance of Pools ....................................................... 8
1.0 Pool Operator .......................................................................................... 8
1.1 Certificate ............................................................................................. 8
1.2 Qualifications obtained prior to November 30, 2014 ............................. 8
1.3 Additional Training ................................................................................ 8
2.0 Pool Maintenance .................................................................................... 8
2.1 Shower water temperature range ......................................................... 8
2.2 Public swimming pool maximum water temperature ............................. 8
2.3 Dry sauna and steam sauna maximum temperature ............................ 8
2.4 Ventilation ............................................................................................. 9
2.5 Monitoring Length of Stay ..................................................................... 9
2.6 Soap in washrooms and showers ......................................................... 9
2.7 Designated food handling and consumption area ................................ 9
2.8 Exemption for soap and shower temperature ....................................... 9
3.0 Filtration, Circulation and Disinfection ...................................................... 9
3.1 Recirculation ......................................................................................... 9
3.2 Collection of water from public swimming pool surface ...................... 10
3.3 Maximum rate of filtration ................................................................... 10
3.4 Treatment for recirculating water spray parks .................................... 11
4.0 Chlorine, pH and Other Chemical Parameters ....................................... 11
4.1 Free chlorine residual ......................................................................... 11
4.2 Oxidation reduction potential (ORP) ................................................... 11
4.3 Combined chlorine residual ................................................................ 11
4.4 pH range ............................................................................................. 11
4.5 Total alkalinity ..................................................................................... 12
4.6 Cyanuric acid ...................................................................................... 12
4.7 Non-chlorinated oxidizing products .................................................... 12
5.0 Testing, Monitoring and Recordkeeping ................................................ 12
5.1 Operating records ............................................................................... 12
5.2 Manual tests ....................................................................................... 13
5.3 Automated controller results ............................................................... 13
6.0 Microbiological Requirements ................................................................ 13
6.1 Heterotrophic plate count / Total coliforms ......................................... 13
6.2 Pseudomonas aeruginosa .................................................................. 13
7.0 Microbiological Sampling ....................................................................... 13
7.1 Water sampling procedure ................................................................. 13
7.2 Collection of water samples ................................................................ 14
8.0 Water Quality and Water Clarity ............................................................ 14
8.1 Bather load ......................................................................................... 14
Page 4
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 4
8.2 Clarity problems.................................................................................. 14
9.0 Anti-Entrapment Devices ....................................................................... 14
9.1 Anti-entrapment Plan .......................................................................... 15
9.2 Installation of anti-entrapment devices ............................................... 15
9.3 Main submerged suction outlet ........................................................... 15
9.4 Single or interconnected submerged suction outlet ............................ 15
9.5 Other submerged suction outlets ........................................................ 16
9.6 Damaged submerged suction outlets ................................................. 16
Part 4 Written Policies and Plans ..................................................................... 17
10.0 Pool Safety and Supervision .............................................................. 17
10.1 Pool Safety and Supervision Plan ...................................................... 17
11.0 Patron Education and Notification ...................................................... 18
11.1 Education of patrons ........................................................................... 18
11.2 Signs posting rules and safety information ......................................... 18
12.0 Water Quality Incident Response Plan ............................................... 19
12.1 Water Quality Incident Response Plan ............................................... 19
12.2 Requirements ..................................................................................... 19
13.0 General Sanitation Plan ...................................................................... 19
13.1 General Sanitation Plan ...................................................................... 20
Part 5 Schedules .............................................................................................. 21
Schedule A ...................................................................................................... 21
Contamination Management for Public Swimming Pools ............................ 21
Public Swimming Pool Water Contamination Response .............................. 22
Schedule B ...................................................................................................... 24
Calculation for the Maximum Bather Load ................................................... 24
Schedule C ..................................................................................................... 25
Flow Capacity Requirements for Submerged Suction Outlets ..................... 25
Page 5
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 5
Part 1 Purpose and Application
Introduction
The Pool Standards, July 2014 are established under the authority of the Public Health
Act, RSA 2000, c P-37 (Act) and the Public Swimming Pools Regulation (Regulation) (AR
204/2014). They have been developed in consultation with the pool industry, pool
operators and public health officials from Alberta Health Services. The Pool Standards,
July 2014(Amended January 2018) replace the Pool Standards, July 2014 (Amended 2017).
Purpose
The primary objective of the Pool Standards is to set specific technical standards
pertaining to water quality and facility operations required in the Regulation.
The Pool Standards set requirements for operator education, recirculation, water
chemistry and microbiology, water quality monitoring, anti-entrapment, policies and
plans related to pool safety and supervision, public education, water quality incident
response and general sanitation.
The Pool Standards also include a protocol for management of contaminated public
swimming pool water and the calculations for maximum bather load and flow rates
through anti-entrapment suction outlets.
The Regulation and the Pool Standards together govern the operation and maintenance
of pools to ensure safe water quality and a safe and sanitary swimming environment
for Albertans. The Regulation and the Pool Standards do not govern the operation and
maintenance of floatation tanks.
Application
The Pool Standards apply to all pools as defined in the Regulation.
Pursuant to Section 3 of the Regulation, the Pool Standards do not apply to:
• a structure containing water constructed for the sole use by owners of a single
family dwelling and their families and guests;
• a natural pool; or
• a pool of water that is drained, cleaned and filled after each use by each
individual.
Page 6
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 6
Part 2 Definitions
The following terms are defined in the Regulation and are repeated here for ease of reference:
a) bed and breakfast means a bed and breakfast as defined in the Food Regulation
(AR 31/2006);
b) executive officer means an executive officer as defined in the Public Health Act;
c) natural pool
means an artificially created ecosystem which reproduces the
conditions of a natural body of water where water is purified by
biological and physical treatment;
d) owner means the owner of a pool;
e) owner’s agent means the person designated under section 5 as an owner’s agent;
f) patron means an individual who enters the public swimming pool
premises and might or might not enter or use the public swimming
pool;
g) pool means a public swimming pool and the public swimming pool’s
premises;
h) pool operator means an individual who operates and maintains a pool on a day-
to-day basis and meets the qualifications set out in the Pool
Standards in order to do so;
i) Pool Standards means the Pool Standards, July 2014 (Amended January 2018) declared
in force by section 2;
j) public swimming
pool
means a structure that contains water that is used for recreational,
therapeutic or other similar purposes and includes a swimming
pool, wading pool, water spray park, whirlpool and any fountain or
other artificially created pool of water;
k) public swimming
pool premises
l) suction outlet
means the buildings and equipment used in connection with a
public swimming pool;
means a fitting or fitting assembly and related components,
including a cover or grate and sump, that provide a localized low
pressure area for the transfer of water from a public swimming
pool;
m) swimming pool means a structure that contains water that is deeper than 60
centimetres at its deepest point.
Page 7
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 7
n) wading pool means a structure containing water the depth of which is 60
centimetres or less throughout the structure;
o) water spray park means a structure on which water is sprayed or released but does
not accumulate;
p) whirlpool means a structure containing water at a temperature above 30°C
and that:
(i) is not drained, cleaned and refilled before use by each
individual, and
(ii) utilizes hydro-jet circulation or air induction bubbles or both.
For the purposes of the Pool Standards, the following terms are defined:
anti-entrapment device means any device used for the purpose of preventing body
entrapment, hair entrapment or entanglement, limb entrapment,
mechanical entrapment, evisceration incidents and death including
but not limited to: certified ANSI/APSP-16 2011 suction outlets, a
Safety Vacuum Release System (SVRS), a suction-limiting vent
system or an automatic pump shut off system.
bather means a patron who enters or uses the public swimming pool.
blockable suction outlet means a suction outlet that has a perforated (open) area that can be
shadowed by the area of the 18 x 23 inches (45.7 x 58.4
centimeters) body blocking element described in ANSI/APSP – 16
2011.
maximum flow rate means the highest possible water flow through a fully submerged
suction system (excluding the skimmer or gutter system) with the
system’s pump(s) operating at full speed with clean pump basket(s)
and clean filter(s).
secondary disinfection means a disinfection process or system designed to achieve
minimum 3-log (99.9 percent) reduction in the number of infective
cryptosporidium oocysts.
Page 8
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 8
Part 3 Operation and Maintenance of Pools
1.0 Pool Operator
For the purposes of section 6 of the Regulation, the following pool operator training
and certification qualifications apply.
1.1 Certificate
The pool operator must
a) be certified by an organization that is on the List of Approved Pool
Operator Education Organizations approved by the Minister, and
b) upon request, provide proof of successful completion of the course in
the form of a certificate issued by the approved organization.
1.2 Qualifications obtained prior to November 30, 2014
A pool operator is considered certified if, prior to November 30, 2014, the
pool operator
a) has successfully completed a pool operator course through the Alberta
Association of Recreation Facility Personnel, the National Swimming
Pool Foundation, or a regional health authority in Alberta, and
b) is operating a pool or teaching a pool course.
1.3 Additional Training
An executive officer may require a pool operator to obtain additional training
in water treatment, disinfection, facility operation and safety where required.
2.0 Pool Maintenance
For the purposes of section 11 of the Regulation, the following pool maintenance
standards apply.
2.1 Shower water temperature range
Subject to section 2.8, every shower must provide water at a temperature of
not less than 35 degrees Celsius and not greater than 45 degrees Celsius.
2.2 Public swimming pool maximum water temperature
2.2.1 The water in a public swimming pool, when in use, must not be
greater than 40 degrees Celsius.
2.2.2 A whirlpool must be fitted with a temperature regulator that is in
good working order.
2.3 Dry sauna and steam sauna maximum temperature
2.3.1 The ambient air temperature in a dry sauna must not be greater than
85 degrees Celsius.
Page 9
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 9
2.3.2 The ambient air temperature in a steam sauna must not be greater
than 60 degrees Celsius.
2.3.3 The ambient air temperature in a dry sauna or a steam sauna must be
measured and recorded at least once every 24-hours, when in use.
2.4 Ventilation
The ventilation in a public swimming pool premises must be able to maintain
safe air quality and must protect against the buildup of chlorine gas or
disinfection by-products.
2.5 Monitoring Length of Stay
2.5.1 To assist patrons in monitoring their length of stay in a whirlpool, a
clock must be clearly visible from the whirlpool.
2.5.2 Reasonable provisions shall be available to assist patrons in
monitoring their length of stay in a dry sauna or steam sauna. These
could include, but are not limited to, supervision, clocks or timing
devices that use sound or light.
2.6 Soap in washrooms and showers
Subject to section 2.8, an adequate supply of soap must be provided in
suitable dispensers in all washrooms and showers.
2.7 Designated food handling and consumption area
Any food handling and consumption must occur in a clearly designated area
which is set aside for that purpose.
2.8 Exemption for soap and shower temperature
Sections 2.1 and 2.6 do not apply to showers used only for cooling or rinsing
purposes.
3.0 Filtration, Circulation and Disinfection
For the purposes of sections 10, 12 and 13 of the Regulation, the following filtration,
circulation, disinfection and operational standards apply.
3.1 Recirculation
3.1.1 A recirculation rate shall be maintained so that an amount of water
equivalent to 100 percent of the water volume passes through
treatment and is recirculated within:
i. 4 hours, for a swimming pool constructed after November 2006,
ii. 6 hours, for a swimming pool constructed before November
2006,
Page 10
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 10
iii. 8 hours, for a swimming pool constructed before November
2006, where it can be demonstrated that the water quality can be
maintained in accordance with the Pool Standards.
iv. 1.5 hours for a water slide receiving pool used solely for that
purpose.
v. 2 hours for a stand-alone wading pool or recirculating water spray
park.
vi. 15 minutes for a whirlpool with a volume of less than four cubic
metres.
vii. 20 minutes for a whirlpool with a volume of four or more cubic
metres.
3.1.2 Notwithstanding section 3.1.1, a water slide receiving pool or
whirlpool constructed prior to November 30, 2006, may exceed the
required recirculation rates if chlorine, pH, clarity, oxidation
reduction potential (ORP) and bacteriological requirements are
maintained in accordance with Sections 4.0, 6.0 and 8.0 of the Pool
Standards.
3.1.3 If a wading pool, water slide receiving pool or recirculating water
spray park is connected to a swimming pool, the turnover time for
the swimming pool shall apply to the wading pool, water slide
receiving pool or water spray park.
3.2 Collection of water from public swimming pool surface
When a public swimming pool is in use, it must be operated to maximize the
flow of the water through the skimming devices.
3.3 Maximum rate of filtration
3.3.1 The maximum rate of filtration for a high rate sand filter must not
be:
a) greater than 10 litres per second per square meter (15 US gallons
per minute per square foot) for swimming pools, water slide
receiving pools, wading pools or recirculating water spray parks,
and
b) greater than 8.5 litres per second per square meter (12.5 US
gallons per minute per square foot) for a whirlpool.
3.3.2 Notwithstanding subsection 3.3.1, pools constructed prior to
November 30, 2006, that use high rate sand filters may operate at a
higher filtration rate where
a) the rate is prescribed by the manufacturer’s specifications, and
b) where the chlorine, pH, clarity, ORP and bacteriological
requirements can be maintained in accordance with Sections 4.0,
6.0 and 8.0 of the Pool Standards.
Page 11
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 11
3.3.3 The rate of filtration for other types of filters must comply with the
manufacturer’s specifications.
3.4 Treatment for recirculating water spray parks
Any stand-alone recirculating water spray park constructed after November
30, 2014 shall provide 100 per cent filtered water with 2.0 milligrams per litre
free chlorine residual at the point of contact with the bather.
4.0 Chlorine, pH and Other Chemical Parameters
For the purposes of sections 13 and 14 of the Regulation, the following chlorine, pH
and other chemical parameter standards apply.
4.1 Free chlorine residual
The minimum free chlorine residual in a public swimming pool must be
maintained as follows:
4.1.1 1.0 milligram per litre in a public swimming pool with an operating
water temperature of not greater than 30 degrees Celsius.
4.1.2 2.0 milligrams per litre in a public swimming pool with an operating
water temperature of greater than 30 degrees Celsius.
4.1.3 2.0 milligrams per litre in a recirculating, stand-alone water spray park
or stand-alone wading pool regardless of the operating water
temperature.
4.2 Oxidation reduction potential (ORP)
Notwithstanding standard 4.1, a public swimming pool, except for a
recirculating water spray park, may operate with a free chlorine residual of no
less than:
a) 0.5 milligrams per litre if able to consistently maintain an ORP value of
no less than 700 millivolt (mV), and
b) 0.3 milligrams per litre if able to consistently maintain an ORP value of
no less than 770 mV, a pH of no more than 7.3 and when supplemental
disinfection is used.
4.3 Combined chlorine residual
The combined chlorine residual in a public swimming pool must be
maintained at the lowest level possible to maximize bather comfort.
4.4 pH range
The pH of the water in a public swimming pool must be maintained at no
less than 6.8 and no greater than 7.6.
Page 12
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 12
4.5 Total alkalinity
4.5.1 The total alkalinity of the public swimming pool water must be
maintained at no less than 60 milligrams per litre and no greater than
180 milligrams per litre, or at levels where chlorine and pH
requirements can be maintained in accordance with Section 4.0 of the
Pool Standards.
4.5.2 Total alkalinity must be measured and recorded at least once per
week.
4.6 Cyanuric acid
Where cyanuric acid is used in an outdoor public swimming pool, the
concentration:
a) must not be greater than 50 milligrams per litre, and
b) must be measured and recorded at least once a week.
4.7 Non-chlorinated oxidizing products
Non-chlorinated oxidizing products used in a public swimming pool must be
used in accordance with the manufacturer’s instructions.
5.0 Testing, Monitoring and Recordkeeping
For the purposes of section 15 and 17 of the Regulation, the following monitoring and
recordkeeping standards apply.
5.1 Operating records
Operating records must be maintained to provide information regarding:
a) time of and observations and readings for pH, and the free, total and
combined chlorine residual;
b) time and results of total alkalinity tests;
c) automated controller set points and readings for ORP, chlorine and pH;
d) temperature of the public swimming pool water;
e) clarity of the water;
f) results of microbiological analyses as provided by the regional health
authority;
g) any other water quality tests;
h) quantities and dates of all chemicals used;
i) equipment maintenance, including pump modifications which potentially
affect flow rate;
j) ambient air temperature in a dry sauna or steam sauna;
Page 13
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 13
k) make and model, purchase and expiry date of suction outlet covers, and
manufacturers’ recommended flow rate;
l) incident records with respect to patron injury; and
m) contamination events including the date of the event and the response.
5.2 Manual tests
5.2.1 The free chlorine, combined chlorine and pH must be tested
manually at least once per day:
5.2.2 The automated readings and associated setpoints shall be monitored
and recorded at least once per day.
5.2.3 Dip and read strips must not be used to measure chlorine, pH or
alkalinity.
5.3 Automated controller results
Automated controller readings must be consistent with any manual tests.
6.0 Microbiological Requirements
For the purposes of section 18 of the Regulation, the following microbiological
requirements apply.
6.1 Heterotrophic plate count / Total coliforms
The quality of water in a public swimming pool must be maintained so that
the water does not:
a) have a heterotrophic plate count greater than 100 colony forming units
per milliliter in a 100 millilitre sample, or
b) show the presence of total coliforms in a 100 millilitre sample.
6.2 Pseudomonas aeruginosa
In addition to 6.1, the quality of water in a public swimming pool operating
at greater than 30 degrees Celsius must be maintained so that samples of the
water do not show the presence of Pseudomonas aeruginosa.
7.0 Microbiological Sampling
For the purposes of section 19 of the Regulation, the following microbiological
sampling requirements apply.
7.1 Water sampling procedure
7.1.1 A water sample for heterotrophic plate count and total coliforms
must be taken weekly from a public swimming pool.
Page 14
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 14
7.1.2 A water sample for Pseudomonas aeruginosa must be taken weekly for
public swimming pools operating at 30 degrees Celsius or greater.
7.1.3 Samples required under Section 7.1.1 and 7.1.2 must be taken:
a) from a point near an outlet or from any other location that is
necessary to give an accurate representation of the water quality
in the public swimming pool, and
b) between 200 to 400 millimeters below the surface of the water.
7.2 Collection of water samples
Public swimming pool water samples for microbiological testing must be
collected in sample bottles supplied by the Provincial Laboratory of Public
Health (ProvLab).
8.0 Water Quality and Water Clarity
For the purposes of sections 10 and 20 of the Regulation, the following public
swimming pool water quality and clarity standards apply.
8.1 Bather load
8.1.1 When in use, the maximum design bather load of the public
swimming pool must not be exceeded.
8.1.2 Where the maximum design bather load for a public swimming pool
is not available, the owner or owners’ agent, if any, must calculate and
apply a maximum bather load value in accordance with Schedule B.
8.1.3 Notwithstanding 8.1.1 and 8.1.2, the public swimming pool may be
operated to exceed the maximum design bather load or the calculated
maximum bather load if chlorine, pH, clarity, ORP and
bacteriological requirements are met.
8.2 Clarity problems
Where water clarity problems persist, the executive officer may require
monitoring of the clarity until the turbidity is no greater than 0.5
Nephelometric Turbidity Units (NTU).
9.0 Anti-Entrapment Devices
For the purposes of section 23 of the Regulation, the following standards apply.
ANSI/APSP-16 2011 means the Standard 16 American National Standard for Suction
Fittings for Use in Swimming Pools, Wading Pools, Spas and Hot Tubs published by the
American National Standards Institute/Association of Pool and Spa Professionals.
Page 15
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 15
ASTM F2387 means the Standard Specification for Manufactured Safety Vacuum Release
Systems (SVRS) for Swimming Pools, Spas and Hot Tubs published by the American
Society for Testing and Materials.
ASME/ANSI A112.19.17 (previously known as ASME/ANSI A112.19.17-2010)
means the Manufactured Safety Vacuum Release Systems (SVRS) for Residential
and Commercial Swimming Pool, Spa, Hot Tub, and Wading Pool Suction Systems
published by the American Society of Mechanical Engineers/American National
Standards Institute.
9.1 Anti-entrapment Plan
Every owner or owner’s agent, if any, must assess anti-entrapment risks,
develop and implement an appropriate anti-entrapment plan to meet the
requirements of this section.
9.2 Installation of anti-entrapment devices
An anti-entrapment device must be installed in accordance with the
manufacturer’s specifications and be maintained in good working order when
the public swimming pool is in use.
9.3 Main submerged suction outlet
9.3.1 On or after November 30, 2019, a submerged suction outlet,
including a gravity fed outlet, in a public swimming pool, must be:
a. compliant with the ANSI/APSP-16 2011 performance
standards, or
b. custom fabricated and certified by a professional
engineer, in accordance with ANSI/APSP-16 2011, and
installed and maintained according to the engineer’s
instructions.
9.3.2 The flow rating of the submerged suction outlet must be higher than
or equal to the maximum flow rate divided across multiple
interconnected outlets in accordance with Schedule C.
9.3.3 Pursuant to Section 9.3.2, where an operator is unable to calculate the
maximum flow rate, the maximum flow rate must be determined by a
professional engineer.
9.4 Single or interconnected submerged suction outlet
On or after November 30, 2019, an existing public swimming pool that has
i) a blockable single submerged suction outlet, or
ii) interconnected submerged suction outlets with a distance of
less than 66 cm (26 inches) from the outside edge of one cover
to the inside edge of the second cover on the same plane.
must employ at least one of the following systems:
Page 16
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 16
a) a multiple suction outlet system with at least two fully submerged suction
outlets per pump no less than 66 cm (26 inches) from the outside edge of
one cover to the inside edge of the second cover,
b) a safety vacuum release system (commonly referred to as SVRS) that
relieves suction when a blockage is detected and that is installed to meet
the performance standards of the ASTM F2387 or ASME/ANSI
A112.19.17,
c) a properly designed and tested suction-limiting vent system which meets
ASME-A112.19.17,
d) an automatic pump shut-off system which meets ASME-A112.19.17,
e) permanent disablement of the submerged suction outlet either by
reversing the flow through the outlet or completely sealing the existing
outlet if the skimmers are capable of providing for 100 percent flow
through,
f) a gravity fed system, or equivalent system, approved by a professional
engineer, or
g) interconnected submerged suction outlets on different planes, not
installed in a seating area.
9.5 Other submerged suction outlets
Notwithstanding sections 9.3 and 9.4, every equalizer line outlet or
submerged suction outlet used for vacuuming must
a. have a cover to prevent the risk of entrapment, or
b. be permanently disabled.
9.6 Damaged submerged suction outlets
9.6.1 The covers of each submerged suction outlet, including equalizer and
vacuum outlets, shall be routinely inspected prior to opening each
day and throughout the day when the public swimming pool is in use.
9.6.2 If upon visual inspection the cover of a submerged suction outlet is
cracked, broken, improperly secured or missing, the pump shall be
immediately shut down and the public swimming pool closed, and
only reopened when the cover is repaired or replaced.
9.6.3 Notwithstanding 9.6.2, an executive officer, where satisfied that
measures undertaken by the operator will sufficiently protect bathers
from entrapment, may allow a swimming pool to remain open to the
public until repair or replacement of the cover can be conducted.
9.6.4 An anti-entrapment system installed in accordance with Section 9.4
must be routinely inspected in accordance with manufacturers’
instructions. A pool shall be closed immediately if the anti-
entrapment system is not operating in accordance with the
manufacturer’s instructions.
Page 17
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 17
Part 4 Written Policies and Plans
For the purposes of section 24 of the Regulation, the following standards for written policies
and plans apply.
10.0 Pool Safety and Supervision
10.1 Pool Safety and Supervision Plan
A Pool Safety and Supervision Plan shall be developed based on current best
practices, and must include:
a) a pool admission standard based on the bather’s age, swimming
competency and adult oversight if the bather is a minor or when there is
a question of swimmer competency;
b) rules for bather use and supervision of pool mats, inflatable toys and life
jackets;
c) a list of all of the facility-appropriate lifesaving equipment to be provided
on-site;
d) a list of the required emergency equipment and procedures including
telephone access and emergency telephone numbers;
e) a facility safety check procedure;
f) supervision protocols including lifeguard scanning and supervision
protocols for each public swimming pool when in use, including those
not offering lifeguarding;
g) Information and procedures for use of a public swimming pool where no
lifeguard is on duty;
h) a procedure to monitor patrons using special areas such as the dry sauna
and steam sauna;
i) procedures to respond to medical emergencies such as entrapped
patrons, overheated dry sauna or steam sauna users;
j) measures to ensure the safety of patrons using a dry sauna or steam sauna
in order to protect against burns and overheating which may include, but
are not limited to:
• thermostatic control of air temperature,
• a working thermometer in each unit,
• doors that open outwards with little resistance,
• a signaling device or process for emergencies;
k) information on the safe handling and storage of pool treatment chemicals
and other related chemicals; and
l) any other measure that may be applicable to the pool.
Page 18
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 18
11.0 Patron Education and Notification
For the purposes of Section 24 of the Regulation, the following education and signage
standards apply.
11.1 Education of patrons
11.1.1 The patron education policy and plan shall include a strategy to
provide information to:
a) those bathers who should wear protective, water-resistant
swimwear including
i) children, 35 months and under, and
ii) anyone who is or may be incontinent.
b) those patrons who should consult with a physician prior to using
the whirlpool, dry sauna and steam sauna, including
i) pregnant women,
ii) individuals with medical conditions including but not limited
to heart disease, hypertension, seizures, diabetes or obesity,
iii) individuals greater than 65 years of age; and
iv) individuals with a medical condition requiring the ongoing
care of a physician.
c) those patrons with diarrhea or a history of diarrhea over the
previous two weeks who should not use the public swimming
pool.
11.2 Signs posting rules and safety information
Except for stand-alone water spray parks, an owner or owner’s agent, if any,
must post one or more signs that convey the following rules and safety
information for the use of the pool in a size, type and location that may be
easily seen by all patrons.
Rules for use of the pool
11.2.1 Bathers must take a shower using soap prior to entering the public
swimming pool.
11.2.2 Patrons must wash their hands using soap after using the washroom
or changing diapers.
11.2.3 Glass is not allowed on the pool deck or in other barefoot areas.
11.2.4 Street footwear must not be worn in wet traffic areas.
11.2.5 Patrons who are intoxicated will not be allowed to use the pool.
Pool safety information________________________________________
Page 19
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 19
11.2.6 The maximum bather load for the public swimming pool.
11.2.7 The public swimming pool depths and identification of those areas of
the public swimming pool where diving is not allowed.
11.2.8 The permitted temperature range of the whirlpool, dry sauna or
steam sauna.
11.2.9 Location of the fire alarm, telephone or other emergency devices,
where applicable.
11.2.10 Where there is no lifeguard on duty, signage stating
• No lifeguard is on duty,
• Children under 13 years of age should be supervised, and
• Patrons should not swim alone.
11.2.11 Any other information that the owner or owner’s agent determines is
necessary to maintain the health and safety of the patrons using the
pool facility.
12.0 Water Quality Incident Response Plan
For purposes of section 24 of the Regulation, the following water quality response standards
apply.
12.1 Water Quality Incident Response Plan
A Water Quality Incident Response Plan that is appropriate to the type of
public swimming pool must include the following:
a) the steps to be taken when any of the following occur:
i) standards for microbiology, ORP, free chlorine, cyanuric acid, pH
and clarity in the public swimming pool are not being met,
ii) blood, food or chemicals foul the water, or
iii) fecal material or vomit foul the water, and
b) the name of the appropriate contact person and emergency contact
numbers.
12.2 Requirements
A Water Quality Incident Response Plan must adhere to the requirements in
Schedule A: “Contamination Management for Public Swimming Pools”.
13.0 General Sanitation Plan
For purposes of section 24 of the Regulation, the following standards for the general
sanitation plan apply.
Page 20
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 20
13.1 General Sanitation Plan
A General Sanitation Plan for a public swimming pool premises must list the
chemicals used for cleaning and disinfection, and specify a routine schedule
for adequate cleaning, and where necessary disinfecting, of:
a) walls, floors, and decks;
b) washrooms and change rooms;
c) showers;
d) dry saunas and steam saunas; and
e) any other area or equipment in contact with patrons of the pool.
Page 21
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 21
Part 5 Schedules
Schedule A
Contamination Management for Public Swimming Pools
Every owner or owner’s agent is required to develop, maintain, and implement a
written policy that outlines a response plan for managing blood, vomit, and fecal
contamination in public swimming pools. This schedule was first developed in 2006,
and has been modified to reflect the United States Centers for Disease Control and
Prevention Recommendations for Aquatic Operators of Treated Venues March 2012.
1. In the event of blood, vomit, or fecal contamination, the pool operator shall
immediately close the public swimming pool until remediation procedures are
complete. This also includes any affected water features and public swimming
pools that share the same recirculation system.
2. To avoid cross contamination, a bather must take a shower, using soap, prior to
re-entering any public swimming pool.
3. Contaminating material must be removed (e.g. using a net, scoop, or bucket) and
disposed of in a sanitary manner.
4. The net, scoop or container used to remove the fecal or vomit contamination
must be thoroughly cleaned and disinfected.
5. Aquatic vacuum cleaners must not be used for removal of contaminants from
the water or adjacent surfaces unless vacuumed waste is discharged to a sanitary
sewer and the vacuum equipment can be adequately cleaned and disinfected.
6. A contamination response log must be maintained and must include at a
minimum:
• the date and time of the event,
• type of incident,
• the concentration of chlorine, pH and ORP at the time of the incident,
• the procedures followed, and
• the name of the person(s) conducting the procedures.
Page 22
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 22
Public Swimming Pool Water Contamination Response
For purposes of this section, CT means concentration in milligrams per litre
multiplied by time in minutes. CT=C (mg/L) X T (min)
1. A public swimming pool that has been contaminated by blood, vomit or feces
shall be treated as follows:
a) Check to ensure that the pH of the water is 7.5 or lower and adjust if
necessary;
b) Verify and maintain water temperature at 25 degrees Celsius or higher;
c) Operate the filtration/recirculation system while the water reaches and
maintains the proper free chlorine concentration during the remediation
process; and
d) Test the chlorine residual at multiple sampling points to ensure the proper
free chlorine concentration is achieved throughout the water for the entire
disinfection time.
2. In addition to the above measures, the specific treatment of the water depends
upon the type of contamination. The water should be treated as follows:
Blood-contaminated water
If the public swimming pool is operating at required chlorine residual and pH, it
may remain open. If the free chlorine residual is below the required minimum
residual level, the operator shall immediately close the public swimming pool
until the free chlorine is verified to be at or above the required minimum.
Vomit-contaminated water
Raise the free chlorine residual to 2.0 mg/L (if less than 2.0 mg/L), and maintain
for at least 25 minutes, or meet an equivalent CT value as shown in the table
below.
Formed-fecal contaminated water
Raise the free chlorine residual to 2.0 mg/L and maintain for at least 25 minutes,
or meet an equivalent CT value as shown in the table below.
CT for Response to Formed-Fecal Incident
Chlorine Concentration
(mg/L)
Disinfection
Time
Equivalent CT
Values
1.0 50 minutes 50
2.0 25 minutes 50
3.0 17 minutes 50
The above table is based on the minimum CT of 45, maximum pH of 7.5, minimum temperature
of 25 degrees Celsius and 99.9% inactivation of Giardia cysts by chlorine taken from United States
Centers for Disease Control. Responding to Fecal Accidents in Disinfected Swimming Pool Venues . MMWR
2001:50(20):416-7.
Page 23
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 23
Diarrhea contaminated water
For purposes of this section, diarrhea means stool that is too liquid to form a
constant shape and stool that due to its consistency , cannot be captured in a
standard net.
a) Raise the free chlorine residual to 20.0 milligrams per litre, and maintain for
at least 12.75 hours or
b) Meet an equivalent CT value as shown in the table below.
CT for Response to Diarrhea Incident
Chlorine Concentration
(mg/L)
Disinfection
Time
Equivalent CT
1.0 15,300 minutes
(255 hours)
15,300
10.0 1,530 minutes
(25.5 hours)
15,300
20.0 765 minutes
(12.75 hours)
15,300
The above table is based on a minimum CT of 15,300*, maximum pH of 7.5, minimum
temperature of 25 degrees Celsius and 99.9% inactivation of Cryptosporidium cysts taken from
Shields, JM et al (2008) Inactivation of Cryptosporidium parvum under chlorinated recreational
water conditions, published by Journal of Water and Health. 06.4:513-520.
c) In water containing chlorine stabilizer, lower the cyanuric acid concentration
to 15 milligrams per litre or less, and raise the free chlorine to either 20
milligrams per litre for at least 28 hours, to 30 milligrams per litre for at least 18
hours, or to 40 milligrams per litre for at least 8.5 hours.
3. The owner or owner’s agent, if any, of a public swimming pool may use a
combination of chlorine and other secondary disinfection treatments to respond
to a contamination event. Pursuant to section 8(1) of the Regulation, the
regional health authority must review and approve any secondary disinfection
prior to its use in order to ensure that an equivalent CT value will be achieved.
Page 24
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 24
Schedule B
Calculation for the Maximum Bather Load
Maximum bather load is the maximum number of bathers allowed in any 24-hour
period based on the capacity of the filtration system. It is determined based on two
cubic meters of treated water for every bather in each 24-hour period, and the
turnover period.
To determine the volume of treated water produced by the public swimming
pool treatment system:
1. Determine the amount of treated water per minute:
Volume of Public swimming pool
_____(cubic metres)______
Turnover period (minutes)
= Volume of treated water
per minute
2. Determine amount of treated water per hour:
Volume of treated water per minute
X 60 minutes = Volume of treated water
per hour
3. Determine the amount of treated water for each day
Volume of treated water per hour
X 24-hours = Volume of treated water
per day (24-hours)
To determine maximum bather load:
Two cubic meters treated water is required for every bather in each 24-hours:
4. Number of bathers over a 24-hour period =
Volume of treated water per day (24-hours)
Two cubic metres per 24-hours
Note: This is equivalent to the total number of bathers allowed when the
public swimming pool is in use.
5. If the public swimming pool operates for less than 24-hours then, the number of
bathers per hour =
Number of bathers per 24-hours
Number of hours of operation
Page 25
Alberta Health, Public Health and Compliance
Pool Standards, July 2014 (Amended January 2018)
© 2014–2018 Government of Alberta 25
Schedule C
Flow Capacity Requirements for Submerged Suction Outlets
For the purposes of Section 9.3.2, this table outlines the percent of the maximum
flow rate that each submerged suction outlet must be capable of accommodating.
For systems with multiple interconnected outlets per pump, this is based on the
assumption that one of the outlets is blocked. For example, if a pool had 4
interconnected outlets, the system must be engineered so that each of the remaining
outlets is capable of handling 33% of the maximum flow rate if one is blocked.
2 outlets
in total
3 outlets
in total
4 outlets
in total
5 outlets
in total
6 outlets
in total
>6 outlets
in total
Percent of
maximum flow
rate through
each outlet.
100% 50% 33% 25% 20% 100% / [# of
interconnected
outlets -1]
Links Found